Horizontal Concealed Fan Coil Unit
Built for horizontal false-ceiling installation to save interior space, combining low noise levels, high-efficiency copper tube heat exchangers, and flexible duct connection options for optimal indoor comfort.
Catalogue configurations are listed separately below. Select the water circuit, coil and motor configuration before comparing ratings.
2-pipe system, 3-row coil, AC motor
H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.
Rated airflow
| Model |
High (m³/h) |
Medium (m³/h) |
Low (m³/h) |
| FP-34 |
340 |
260 |
170 |
| FP-51 |
510 |
390 |
260 |
| FP-68 |
680 |
510 |
340 |
| FP-85 |
850 |
640 |
430 |
| FP-102 |
1020 |
770 |
510 |
| FP-136 |
1360 |
1020 |
680 |
| FP-170 |
1700 |
1280 |
850 |
| FP-204 |
2040 |
1530 |
1020 |
| FP-238 |
2380 |
1790 |
1190 |
High-speed performance
| Model |
Cooling (W) |
Heating (W) |
Input (W) |
Noise dB(A) |
| FP-34 |
1850 |
2800 |
36 |
37 |
| FP-51 |
2760 |
4150 |
50 |
39 |
| FP-68 |
3650 |
5500 |
60 |
41 |
| FP-85 |
4535 |
7180 |
74 |
43 |
| FP-102 |
5460 |
8695 |
93 |
45 |
| FP-136 |
7270 |
11190 |
130 |
46 |
| FP-170 |
9080 |
13875 |
147 |
48 |
| FP-204 |
10850 |
16300 |
183 |
50 |
| FP-238 |
12600 |
18900 |
221 |
52 |
Capacity in kcal/h
| Model |
Cooling |
Heating |
| FP-34 |
1591 |
2408 |
| FP-51 |
2374 |
3569 |
| FP-68 |
3139 |
4730 |
| FP-85 |
3900 |
6175 |
| FP-102 |
4695 |
7478 |
| FP-136 |
6252 |
9623 |
| FP-170 |
7809 |
11933 |
| FP-204 |
9331 |
14018 |
| FP-238 |
10836 |
16254 |
Water circuit and weight
| Model |
Water flow (kg/h) |
Pressure loss (kPa) |
Weight (kg) |
| FP-34 |
318 |
≤20 |
10.6 |
| FP-51 |
475 |
≤30 |
12.6 |
| FP-68 |
628 |
≤30 |
13.6 |
| FP-85 |
780 |
≤30 |
15.2 |
| FP-102 |
939 |
≤40 |
16.2 |
| FP-136 |
1250 |
≤40 |
23.1 |
| FP-170 |
1561 |
≤40 |
24.4 |
| FP-204 |
1866 |
≤40 |
27.6 |
| FP-238 |
2167 |
≤50 |
30.9 |
Fan and motor quantities
| Model |
Fans |
Motors |
| FP-34 |
1 |
1 |
| FP-51 |
2 |
1 |
| FP-68 |
2 |
1 |
| FP-85 |
2 |
1 |
| FP-102 |
2 |
1 |
| FP-136 |
3 |
2 |
| FP-170 |
4 |
2 |
| FP-204 |
4 |
2 |
| FP-238 |
4 |
2 |
Input power at high speed
| Model |
12 Pa (W) |
30 Pa (W) |
50 Pa (W) |
| FP-34 |
36 |
43 |
48 |
| FP-51 |
50 |
57 |
64 |
| FP-68 |
60 |
70 |
81 |
| FP-85 |
74 |
84 |
97 |
| FP-102 |
93 |
105 |
114 |
| FP-136 |
130 |
151 |
169 |
| FP-170 |
147 |
169 |
204 |
| FP-204 |
183 |
206 |
243 |
| FP-238 |
221 |
245 |
291 |
Noise at high speed
| Model |
12 Pa dB(A) |
30 Pa dB(A) |
50 Pa dB(A) |
| FP-34 |
37 |
40 |
42 |
| FP-51 |
39 |
42 |
44 |
| FP-68 |
41 |
44 |
46 |
| FP-85 |
43 |
46 |
47 |
| FP-102 |
45 |
47 |
49 |
| FP-136 |
46 |
48 |
50 |
| FP-170 |
48 |
50 |
52 |
| FP-204 |
50 |
52 |
54 |
| FP-238 |
52 |
54 |
56 |
Cabinet options
| Model |
Without return-air box (kg) |
With return-air box (kg) |
| FP-34 |
10.6 |
13.7 |
| FP-51 |
12.6 |
16.3 |
| FP-68 |
13.6 |
17.7 |
| FP-85 |
15.2 |
19.8 |
| FP-102 |
16.2 |
21.2 |
| FP-136 |
23.1 |
29.3 |
| FP-170 |
24.4 |
30.8 |
| FP-204 |
27.6 |
35 |
| FP-238 |
30.9 |
39.2 |
Construction and connections
| Item |
Specification |
| Water circuit |
2-pipe system |
| Coil |
3-row coil |
| Fan type |
Forward-curved, multi-blade centrifugal fan with double inlet |
| Motor type |
Capacitor-run asynchronous AC motor |
| Motor protection / insulation |
IP20 / Class B |
| Heat exchanger |
Copper tubes with louvered aluminium fins, mechanically expanded |
| Water inlet and outlet connections |
3/4 inch internal thread |
| Condensate connection |
3/4 inch external thread |
| Power supply |
220 V / 50 Hz |
Rated conditions and notes
- Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
- Heating rating: inlet water temperature 60°C; water flow the same as for cooling; entering air dry-bulb 21.0°C.
- Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
- For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
- Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
- For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
- The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.
2-pipe system, 4-row coil, AC motor
H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.
Rated airflow
| Model |
High (m³/h) |
Medium (m³/h) |
Low (m³/h) |
| FP-34 |
340 |
260 |
170 |
| FP-51 |
510 |
390 |
260 |
| FP-68 |
680 |
510 |
340 |
| FP-85 |
850 |
640 |
430 |
| FP-102 |
1020 |
770 |
510 |
| FP-136 |
1360 |
1020 |
680 |
| FP-170 |
1700 |
1280 |
850 |
| FP-204 |
2040 |
1530 |
1020 |
| FP-238 |
2380 |
1790 |
1190 |
High-speed performance
| Model |
Cooling (W) |
Heating (W) |
Input (W) |
Noise dB(A) |
| FP-34 |
2240 |
3690 |
39 |
38 |
| FP-51 |
3610 |
5534 |
54 |
40 |
| FP-68 |
4610 |
7380 |
64 |
42 |
| FP-85 |
5630 |
8154 |
82 |
44 |
| FP-102 |
6820 |
10039 |
101 |
46 |
| FP-136 |
8179 |
12798 |
136 |
47 |
| FP-170 |
10260 |
15812 |
159 |
49 |
| FP-204 |
11550 |
18973 |
191 |
51 |
| FP-238 |
13400 |
21677 |
242 |
53 |
Capacity in kcal/h
| Model |
Cooling |
Heating |
| FP-34 |
1926 |
3173 |
| FP-51 |
3105 |
4759 |
| FP-68 |
3965 |
6347 |
| FP-85 |
4842 |
7012 |
| FP-102 |
5865 |
8634 |
| FP-136 |
7034 |
11006 |
| FP-170 |
8824 |
13598 |
| FP-204 |
9933 |
16317 |
| FP-238 |
11524 |
18642 |
Water circuit and weight
| Model |
Water flow (kg/h) |
Pressure loss (kPa) |
Weight (kg) |
| FP-34 |
385 |
≤20 |
11.8 |
| FP-51 |
621 |
≤30 |
13.5 |
| FP-68 |
793 |
≤30 |
14.6 |
| FP-85 |
968 |
≤30 |
16.2 |
| FP-102 |
1173 |
≤40 |
17.8 |
| FP-136 |
1407 |
≤40 |
23.1 |
| FP-170 |
1764 |
≤40 |
29.9 |
| FP-204 |
1986 |
≤40 |
37.2 |
| FP-238 |
2304 |
≤50 |
41.4 |
Fan and motor quantities
| Model |
Fans |
Motors |
| FP-34 |
1 |
1 |
| FP-51 |
2 |
1 |
| FP-68 |
2 |
1 |
| FP-85 |
2 |
1 |
| FP-102 |
2 |
1 |
| FP-136 |
3 |
2 |
| FP-170 |
4 |
2 |
| FP-204 |
4 |
2 |
| FP-238 |
4 |
2 |
Input power at high speed
| Model |
12 Pa (W) |
30 Pa (W) |
50 Pa (W) |
| FP-34 |
39 |
48 |
56 |
| FP-51 |
54 |
62 |
69 |
| FP-68 |
64 |
76 |
88 |
| FP-85 |
82 |
91 |
103 |
| FP-102 |
101 |
116 |
128 |
| FP-136 |
136 |
159 |
185 |
| FP-170 |
159 |
179 |
210 |
| FP-204 |
191 |
218 |
256 |
| FP-238 |
242 |
258 |
306 |
Noise at high speed
| Model |
12 Pa dB(A) |
30 Pa dB(A) |
50 Pa dB(A) |
| FP-34 |
38 |
41 |
43 |
| FP-51 |
40 |
43 |
45 |
| FP-68 |
42 |
45 |
47 |
| FP-85 |
44 |
47 |
48 |
| FP-102 |
46 |
48 |
50 |
| FP-136 |
47 |
49 |
51 |
| FP-170 |
49 |
51 |
53 |
| FP-204 |
51 |
53 |
55 |
| FP-238 |
53 |
55 |
57 |
Cabinet options
| Model |
Without return-air box (kg) |
With return-air box (kg) |
| FP-34 |
11.8 |
15 |
| FP-51 |
13.5 |
17.3 |
| FP-68 |
14.6 |
18.6 |
| FP-85 |
16.2 |
20.7 |
| FP-102 |
17.8 |
22.8 |
| FP-136 |
23.1 |
28.8 |
| FP-170 |
29.9 |
36.9 |
| FP-204 |
37.2 |
45.2 |
| FP-238 |
41.4 |
50 |
Construction and connections
| Item |
Specification |
| Water circuit |
2-pipe system |
| Coil |
4-row coil |
| Fan type |
Forward-curved, multi-blade centrifugal fan with double inlet |
| Motor type |
Capacitor-run asynchronous AC motor |
| Motor protection / insulation |
IP20 / Class B |
| Heat exchanger |
Copper tubes with louvered aluminium fins, mechanically expanded |
| Water inlet and outlet connections |
3/4 inch internal thread |
| Condensate connection |
3/4 inch external thread |
| Power supply |
220 V / 50 Hz |
Rated conditions and notes
- Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
- Heating rating: inlet water temperature 60°C; water flow the same as for cooling; entering air dry-bulb 21.0°C.
- Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
- For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
- Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
- For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
- The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.
4-pipe system, 3+1-row coil, AC motor
H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.
Rated airflow
| Model |
High (m³/h) |
Medium (m³/h) |
Low (m³/h) |
| FP-34 |
340 |
260 |
170 |
| FP-51 |
510 |
390 |
260 |
| FP-68 |
680 |
510 |
340 |
| FP-85 |
850 |
640 |
430 |
| FP-102 |
1020 |
770 |
510 |
| FP-136 |
1360 |
1020 |
680 |
| FP-170 |
1700 |
1280 |
850 |
| FP-204 |
2040 |
1530 |
1020 |
| FP-238 |
2380 |
1790 |
1190 |
High-speed performance
| Model |
Cooling (W) |
Heating (W) |
Input (W) |
Noise dB(A) |
| FP-34 |
1850 |
1800 |
39 |
38 |
| FP-51 |
2760 |
2750 |
54 |
40 |
| FP-68 |
3650 |
3570 |
64 |
42 |
| FP-85 |
4535 |
4250 |
82 |
44 |
| FP-102 |
5460 |
5410 |
101 |
46 |
| FP-136 |
7270 |
6450 |
136 |
47 |
| FP-170 |
9080 |
8620 |
159 |
49 |
| FP-204 |
10850 |
10500 |
191 |
51 |
| FP-238 |
12600 |
11800 |
242 |
53 |
Capacity in kcal/h
| Model |
Cooling |
Heating |
| FP-34 |
1591 |
1617 |
| FP-51 |
2374 |
2365 |
| FP-68 |
3139 |
3070 |
| FP-85 |
3900 |
3655 |
| FP-102 |
4695 |
4653 |
| FP-136 |
6252 |
5547 |
| FP-170 |
7809 |
7413 |
| FP-204 |
9331 |
9030 |
| FP-238 |
10836 |
10148 |
Water circuit and weight
| Model |
Water flow (kg/h) |
Pressure loss (kPa) |
Weight (kg) |
| FP-34 |
318 |
≤20 |
11.8 |
| FP-51 |
475 |
≤30 |
13.5 |
| FP-68 |
628 |
≤30 |
14.6 |
| FP-85 |
780 |
≤30 |
16.2 |
| FP-102 |
939 |
≤40 |
17.8 |
| FP-136 |
1250 |
≤40 |
23.1 |
| FP-170 |
1561 |
≤40 |
29.9 |
| FP-204 |
1866 |
≤40 |
37.2 |
| FP-238 |
2167 |
≤50 |
41.4 |
Fan and motor quantities
| Model |
Fans |
Motors |
| FP-34 |
1 |
1 |
| FP-51 |
2 |
1 |
| FP-68 |
2 |
1 |
| FP-85 |
2 |
1 |
| FP-102 |
2 |
1 |
| FP-136 |
3 |
2 |
| FP-170 |
4 |
2 |
| FP-204 |
4 |
2 |
| FP-238 |
4 |
2 |
Input power at high speed
| Model |
12 Pa (W) |
30 Pa (W) |
50 Pa (W) |
| FP-34 |
39 |
48 |
56 |
| FP-51 |
54 |
62 |
69 |
| FP-68 |
64 |
76 |
88 |
| FP-85 |
82 |
91 |
103 |
| FP-102 |
101 |
116 |
128 |
| FP-136 |
136 |
159 |
185 |
| FP-170 |
159 |
179 |
210 |
| FP-204 |
191 |
218 |
256 |
| FP-238 |
242 |
258 |
306 |
Noise at high speed
| Model |
12 Pa dB(A) |
30 Pa dB(A) |
50 Pa dB(A) |
| FP-34 |
38 |
41 |
43 |
| FP-51 |
40 |
43 |
45 |
| FP-68 |
42 |
45 |
47 |
| FP-85 |
44 |
47 |
48 |
| FP-102 |
46 |
48 |
50 |
| FP-136 |
47 |
49 |
51 |
| FP-170 |
49 |
51 |
53 |
| FP-204 |
51 |
53 |
55 |
| FP-238 |
53 |
55 |
57 |
Cabinet options
| Model |
Without return-air box (kg) |
With return-air box (kg) |
| FP-34 |
11.8 |
15 |
| FP-51 |
13.5 |
17.3 |
| FP-68 |
14.6 |
18.6 |
| FP-85 |
16.2 |
20.7 |
| FP-102 |
17.8 |
22.8 |
| FP-136 |
23.1 |
28.8 |
| FP-170 |
29.9 |
36.9 |
| FP-204 |
37.2 |
45.2 |
| FP-238 |
41.4 |
50 |
Heating water circuit
| Model |
Hot water flow (kg/h) |
| FP-34 |
162 |
| FP-51 |
237 |
| FP-68 |
307 |
| FP-85 |
366 |
| FP-102 |
466 |
| FP-136 |
555 |
| FP-170 |
742 |
| FP-204 |
903 |
| FP-238 |
1015 |
Construction and connections
| Item |
Specification |
| Water circuit |
4-pipe system |
| Coil |
3+1-row coil |
| Fan type |
Forward-curved, multi-blade centrifugal fan with double inlet |
| Motor type |
Capacitor-run asynchronous AC motor |
| Motor protection / insulation |
IP20 / Class B |
| Heat exchanger |
Copper tubes with louvered aluminium fins, mechanically expanded |
| Water inlet and outlet connections |
3/4 inch internal thread |
| Condensate connection |
3/4 inch external thread |
| Power supply |
220 V / 50 Hz |
Rated conditions and notes
- Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
- Heating rating: inlet/outlet water temperatures 60°C / 50°C; entering air dry-bulb 21°C.
- Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
- For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
- Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
- For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
- The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.
4-pipe system, 3-row coil, permanent-magnet synchronous motor
H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.
Rated airflow
| Model |
High (m³/h) |
Medium (m³/h) |
Low (m³/h) |
| FP-34 |
340 |
260 |
170 |
| FP-51 |
510 |
390 |
260 |
| FP-68 |
680 |
510 |
340 |
| FP-85 |
850 |
640 |
430 |
| FP-102 |
1020 |
770 |
510 |
| FP-136 |
1360 |
1020 |
680 |
| FP-170 |
1700 |
1280 |
850 |
| FP-204 |
2040 |
1530 |
1020 |
| FP-238 |
2380 |
1790 |
1190 |
High-speed performance
| Model |
Cooling (W) |
Heating (W) |
Input (W) |
Noise dB(A) |
| FP-34 |
1850 |
2800 |
22 |
37 |
| FP-51 |
2760 |
4150 |
30 |
39 |
| FP-68 |
3650 |
5500 |
36 |
41 |
| FP-85 |
4535 |
7180 |
44 |
43 |
| FP-102 |
5460 |
8695 |
56 |
45 |
| FP-136 |
7270 |
11190 |
78 |
46 |
| FP-170 |
9080 |
13875 |
88 |
48 |
| FP-204 |
10850 |
16300 |
114 |
50 |
| FP-238 |
12600 |
18900 |
139 |
52 |
Capacity in kcal/h
| Model |
Cooling |
Heating |
| FP-34 |
1591 |
2408 |
| FP-51 |
2374 |
3569 |
| FP-68 |
3139 |
4730 |
| FP-85 |
3900 |
6175 |
| FP-102 |
4695 |
7478 |
| FP-136 |
6252 |
9623 |
| FP-170 |
7809 |
11933 |
| FP-204 |
9331 |
14018 |
| FP-238 |
10836 |
16254 |
Water circuit and weight
| Model |
Water flow (kg/h) |
Pressure loss (kPa) |
Weight (kg) |
| FP-34 |
318 |
≤20 |
11 |
| FP-51 |
475 |
≤30 |
12.5 |
| FP-68 |
628 |
≤30 |
13.5 |
| FP-85 |
780 |
≤30 |
15 |
| FP-102 |
939 |
≤40 |
16.5 |
| FP-136 |
1250 |
≤40 |
21.5 |
| FP-170 |
1561 |
≤40 |
28 |
| FP-204 |
1866 |
≤40 |
35 |
| FP-238 |
2167 |
≤50 |
39 |
Fan and motor quantities
| Model |
Fans |
Motors |
| FP-34 |
1 |
1 |
| FP-51 |
2 |
1 |
| FP-68 |
2 |
1 |
| FP-85 |
2 |
1 |
| FP-102 |
2 |
1 |
| FP-136 |
3 |
2 |
| FP-170 |
4 |
2 |
| FP-204 |
4 |
2 |
| FP-238 |
4 |
2 |
Input power at high speed
| Model |
12 Pa (W) |
30 Pa (W) |
50 Pa (W) |
| FP-34 |
22 |
26 |
29 |
| FP-51 |
30 |
34 |
40 |
| FP-68 |
36 |
42 |
49 |
| FP-85 |
44 |
51 |
61 |
| FP-102 |
56 |
65 |
80 |
| FP-136 |
78 |
91 |
101 |
| FP-170 |
88 |
101 |
125 |
| FP-204 |
114 |
140 |
173 |
| FP-238 |
139 |
166 |
208 |
Noise at high speed
| Model |
12 Pa dB(A) |
30 Pa dB(A) |
50 Pa dB(A) |
| FP-34 |
37 |
40 |
42 |
| FP-51 |
39 |
42 |
44 |
| FP-68 |
41 |
44 |
46 |
| FP-85 |
43 |
46 |
47 |
| FP-102 |
45 |
47 |
49 |
| FP-136 |
46 |
48 |
50 |
| FP-170 |
48 |
50 |
52 |
| FP-204 |
50 |
52 |
54 |
| FP-238 |
52 |
54 |
56 |
Cabinet options
| Model |
Without return-air box (kg) |
With return-air box (kg) |
| FP-34 |
11 |
14.2 |
| FP-51 |
12.5 |
16.3 |
| FP-68 |
13.5 |
17.5 |
| FP-85 |
15 |
19.5 |
| FP-102 |
16.5 |
21.5 |
| FP-136 |
21.5 |
27.2 |
| FP-170 |
28 |
35 |
| FP-204 |
35 |
43 |
| FP-238 |
39 |
47.6 |
Construction and connections
| Item |
Specification |
| Water circuit |
4-pipe system |
| Coil |
3-row coil |
| Fan type |
Forward-curved, multi-blade centrifugal fan with double inlet |
| Motor type |
Brushless DC motor, 220 V / 50 Hz, built-in AC-DC conversion |
| Heat exchanger |
Copper tubes with louvered aluminium fins, mechanically expanded |
| Water inlet and outlet connections |
3/4 inch internal thread |
| Condensate connection |
3/4 inch external thread |
| Power supply |
220 V / 50 Hz |
Rated conditions and notes
- Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
- Heating rating: inlet water temperature 60°C; water flow the same as for cooling; entering air dry-bulb 21.0°C.
- Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
- For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
- Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
- For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
- The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.
Technical data: Haichuang catalogue, printed pages 41-44.