Horizontal Concealed Fan Coil Unit

Built for horizontal false-ceiling installation to save interior space, combining low noise levels, high-efficiency copper tube heat exchangers, and flexible duct connection options for optimal indoor comfort.

السمات القيمة
Product type

وحدات لفائف المروحة

Share your required model and operating conditions for technical review.

Horizontal Concealed Fan Coil Unit

Built for horizontal false-ceiling installation to save interior space, combining low noise levels, high-efficiency copper tube heat exchangers, and flexible duct connection options for optimal indoor comfort.

Catalogue configurations are listed separately below. Select the water circuit, coil and motor configuration before comparing ratings.

2-pipe system, 3-row coil, AC motor

H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.

Rated airflow

Model High (m³/h) Medium (m³/h) Low (m³/h)
FP-34 340 260 170
FP-51 510 390 260
FP-68 680 510 340
FP-85 850 640 430
FP-102 1020 770 510
FP-136 1360 1020 680
FP-170 1700 1280 850
FP-204 2040 1530 1020
FP-238 2380 1790 1190

High-speed performance

Model Cooling (W) Heating (W) Input (W) Noise dB(A)
FP-34 1850 2800 36 37
FP-51 2760 4150 50 39
FP-68 3650 5500 60 41
FP-85 4535 7180 74 43
FP-102 5460 8695 93 45
FP-136 7270 11190 130 46
FP-170 9080 13875 147 48
FP-204 10850 16300 183 50
FP-238 12600 18900 221 52

Capacity in kcal/h

Model Cooling Heating
FP-34 1591 2408
FP-51 2374 3569
FP-68 3139 4730
FP-85 3900 6175
FP-102 4695 7478
FP-136 6252 9623
FP-170 7809 11933
FP-204 9331 14018
FP-238 10836 16254

Water circuit and weight

Model Water flow (kg/h) Pressure loss (kPa) Weight (kg)
FP-34 318 ≤20 10.6
FP-51 475 ≤30 12.6
FP-68 628 ≤30 13.6
FP-85 780 ≤30 15.2
FP-102 939 ≤40 16.2
FP-136 1250 ≤40 23.1
FP-170 1561 ≤40 24.4
FP-204 1866 ≤40 27.6
FP-238 2167 ≤50 30.9

Fan and motor quantities

Model Fans Motors
FP-34 1 1
FP-51 2 1
FP-68 2 1
FP-85 2 1
FP-102 2 1
FP-136 3 2
FP-170 4 2
FP-204 4 2
FP-238 4 2

Input power at high speed

Model 12 Pa (W) 30 Pa (W) 50 Pa (W)
FP-34 36 43 48
FP-51 50 57 64
FP-68 60 70 81
FP-85 74 84 97
FP-102 93 105 114
FP-136 130 151 169
FP-170 147 169 204
FP-204 183 206 243
FP-238 221 245 291

Noise at high speed

Model 12 Pa dB(A) 30 Pa dB(A) 50 Pa dB(A)
FP-34 37 40 42
FP-51 39 42 44
FP-68 41 44 46
FP-85 43 46 47
FP-102 45 47 49
FP-136 46 48 50
FP-170 48 50 52
FP-204 50 52 54
FP-238 52 54 56

Cabinet options

Model Without return-air box (kg) With return-air box (kg)
FP-34 10.6 13.7
FP-51 12.6 16.3
FP-68 13.6 17.7
FP-85 15.2 19.8
FP-102 16.2 21.2
FP-136 23.1 29.3
FP-170 24.4 30.8
FP-204 27.6 35
FP-238 30.9 39.2

Construction and connections

Item Specification
Water circuit 2-pipe system
Coil 3-row coil
Fan type Forward-curved, multi-blade centrifugal fan with double inlet
Motor type Capacitor-run asynchronous AC motor
Motor protection / insulation IP20 / Class B
Heat exchanger Copper tubes with louvered aluminium fins, mechanically expanded
Water inlet and outlet connections 3/4 inch internal thread
Condensate connection 3/4 inch external thread
Power supply 220 V / 50 Hz

Rated conditions and notes

  1. Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
  2. Heating rating: inlet water temperature 60°C; water flow the same as for cooling; entering air dry-bulb 21.0°C.
  3. Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
  4. For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
  5. Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
  6. For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
  7. The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.

2-pipe system, 4-row coil, AC motor

H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.

Rated airflow

Model High (m³/h) Medium (m³/h) Low (m³/h)
FP-34 340 260 170
FP-51 510 390 260
FP-68 680 510 340
FP-85 850 640 430
FP-102 1020 770 510
FP-136 1360 1020 680
FP-170 1700 1280 850
FP-204 2040 1530 1020
FP-238 2380 1790 1190

High-speed performance

Model Cooling (W) Heating (W) Input (W) Noise dB(A)
FP-34 2240 3690 39 38
FP-51 3610 5534 54 40
FP-68 4610 7380 64 42
FP-85 5630 8154 82 44
FP-102 6820 10039 101 46
FP-136 8179 12798 136 47
FP-170 10260 15812 159 49
FP-204 11550 18973 191 51
FP-238 13400 21677 242 53

Capacity in kcal/h

Model Cooling Heating
FP-34 1926 3173
FP-51 3105 4759
FP-68 3965 6347
FP-85 4842 7012
FP-102 5865 8634
FP-136 7034 11006
FP-170 8824 13598
FP-204 9933 16317
FP-238 11524 18642

Water circuit and weight

Model Water flow (kg/h) Pressure loss (kPa) Weight (kg)
FP-34 385 ≤20 11.8
FP-51 621 ≤30 13.5
FP-68 793 ≤30 14.6
FP-85 968 ≤30 16.2
FP-102 1173 ≤40 17.8
FP-136 1407 ≤40 23.1
FP-170 1764 ≤40 29.9
FP-204 1986 ≤40 37.2
FP-238 2304 ≤50 41.4

Fan and motor quantities

Model Fans Motors
FP-34 1 1
FP-51 2 1
FP-68 2 1
FP-85 2 1
FP-102 2 1
FP-136 3 2
FP-170 4 2
FP-204 4 2
FP-238 4 2

Input power at high speed

Model 12 Pa (W) 30 Pa (W) 50 Pa (W)
FP-34 39 48 56
FP-51 54 62 69
FP-68 64 76 88
FP-85 82 91 103
FP-102 101 116 128
FP-136 136 159 185
FP-170 159 179 210
FP-204 191 218 256
FP-238 242 258 306

Noise at high speed

Model 12 Pa dB(A) 30 Pa dB(A) 50 Pa dB(A)
FP-34 38 41 43
FP-51 40 43 45
FP-68 42 45 47
FP-85 44 47 48
FP-102 46 48 50
FP-136 47 49 51
FP-170 49 51 53
FP-204 51 53 55
FP-238 53 55 57

Cabinet options

Model Without return-air box (kg) With return-air box (kg)
FP-34 11.8 15
FP-51 13.5 17.3
FP-68 14.6 18.6
FP-85 16.2 20.7
FP-102 17.8 22.8
FP-136 23.1 28.8
FP-170 29.9 36.9
FP-204 37.2 45.2
FP-238 41.4 50

Construction and connections

Item Specification
Water circuit 2-pipe system
Coil 4-row coil
Fan type Forward-curved, multi-blade centrifugal fan with double inlet
Motor type Capacitor-run asynchronous AC motor
Motor protection / insulation IP20 / Class B
Heat exchanger Copper tubes with louvered aluminium fins, mechanically expanded
Water inlet and outlet connections 3/4 inch internal thread
Condensate connection 3/4 inch external thread
Power supply 220 V / 50 Hz

Rated conditions and notes

  1. Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
  2. Heating rating: inlet water temperature 60°C; water flow the same as for cooling; entering air dry-bulb 21.0°C.
  3. Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
  4. For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
  5. Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
  6. For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
  7. The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.

4-pipe system, 3+1-row coil, AC motor

H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.

Rated airflow

Model High (m³/h) Medium (m³/h) Low (m³/h)
FP-34 340 260 170
FP-51 510 390 260
FP-68 680 510 340
FP-85 850 640 430
FP-102 1020 770 510
FP-136 1360 1020 680
FP-170 1700 1280 850
FP-204 2040 1530 1020
FP-238 2380 1790 1190

High-speed performance

Model Cooling (W) Heating (W) Input (W) Noise dB(A)
FP-34 1850 1800 39 38
FP-51 2760 2750 54 40
FP-68 3650 3570 64 42
FP-85 4535 4250 82 44
FP-102 5460 5410 101 46
FP-136 7270 6450 136 47
FP-170 9080 8620 159 49
FP-204 10850 10500 191 51
FP-238 12600 11800 242 53

Capacity in kcal/h

Model Cooling Heating
FP-34 1591 1617
FP-51 2374 2365
FP-68 3139 3070
FP-85 3900 3655
FP-102 4695 4653
FP-136 6252 5547
FP-170 7809 7413
FP-204 9331 9030
FP-238 10836 10148

Water circuit and weight

Model Water flow (kg/h) Pressure loss (kPa) Weight (kg)
FP-34 318 ≤20 11.8
FP-51 475 ≤30 13.5
FP-68 628 ≤30 14.6
FP-85 780 ≤30 16.2
FP-102 939 ≤40 17.8
FP-136 1250 ≤40 23.1
FP-170 1561 ≤40 29.9
FP-204 1866 ≤40 37.2
FP-238 2167 ≤50 41.4

Fan and motor quantities

Model Fans Motors
FP-34 1 1
FP-51 2 1
FP-68 2 1
FP-85 2 1
FP-102 2 1
FP-136 3 2
FP-170 4 2
FP-204 4 2
FP-238 4 2

Input power at high speed

Model 12 Pa (W) 30 Pa (W) 50 Pa (W)
FP-34 39 48 56
FP-51 54 62 69
FP-68 64 76 88
FP-85 82 91 103
FP-102 101 116 128
FP-136 136 159 185
FP-170 159 179 210
FP-204 191 218 256
FP-238 242 258 306

Noise at high speed

Model 12 Pa dB(A) 30 Pa dB(A) 50 Pa dB(A)
FP-34 38 41 43
FP-51 40 43 45
FP-68 42 45 47
FP-85 44 47 48
FP-102 46 48 50
FP-136 47 49 51
FP-170 49 51 53
FP-204 51 53 55
FP-238 53 55 57

Cabinet options

Model Without return-air box (kg) With return-air box (kg)
FP-34 11.8 15
FP-51 13.5 17.3
FP-68 14.6 18.6
FP-85 16.2 20.7
FP-102 17.8 22.8
FP-136 23.1 28.8
FP-170 29.9 36.9
FP-204 37.2 45.2
FP-238 41.4 50

Heating water circuit

Model Hot water flow (kg/h)
FP-34 162
FP-51 237
FP-68 307
FP-85 366
FP-102 466
FP-136 555
FP-170 742
FP-204 903
FP-238 1015

Construction and connections

Item Specification
Water circuit 4-pipe system
Coil 3+1-row coil
Fan type Forward-curved, multi-blade centrifugal fan with double inlet
Motor type Capacitor-run asynchronous AC motor
Motor protection / insulation IP20 / Class B
Heat exchanger Copper tubes with louvered aluminium fins, mechanically expanded
Water inlet and outlet connections 3/4 inch internal thread
Condensate connection 3/4 inch external thread
Power supply 220 V / 50 Hz

Rated conditions and notes

  1. Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
  2. Heating rating: inlet/outlet water temperatures 60°C / 50°C; entering air dry-bulb 21°C.
  3. Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
  4. For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
  5. Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
  6. For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
  7. The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.

4-pipe system, 3-row coil, permanent-magnet synchronous motor

H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.

Rated airflow

Model High (m³/h) Medium (m³/h) Low (m³/h)
FP-34 340 260 170
FP-51 510 390 260
FP-68 680 510 340
FP-85 850 640 430
FP-102 1020 770 510
FP-136 1360 1020 680
FP-170 1700 1280 850
FP-204 2040 1530 1020
FP-238 2380 1790 1190

High-speed performance

Model Cooling (W) Heating (W) Input (W) Noise dB(A)
FP-34 1850 2800 22 37
FP-51 2760 4150 30 39
FP-68 3650 5500 36 41
FP-85 4535 7180 44 43
FP-102 5460 8695 56 45
FP-136 7270 11190 78 46
FP-170 9080 13875 88 48
FP-204 10850 16300 114 50
FP-238 12600 18900 139 52

Capacity in kcal/h

Model Cooling Heating
FP-34 1591 2408
FP-51 2374 3569
FP-68 3139 4730
FP-85 3900 6175
FP-102 4695 7478
FP-136 6252 9623
FP-170 7809 11933
FP-204 9331 14018
FP-238 10836 16254

Water circuit and weight

Model Water flow (kg/h) Pressure loss (kPa) Weight (kg)
FP-34 318 ≤20 11
FP-51 475 ≤30 12.5
FP-68 628 ≤30 13.5
FP-85 780 ≤30 15
FP-102 939 ≤40 16.5
FP-136 1250 ≤40 21.5
FP-170 1561 ≤40 28
FP-204 1866 ≤40 35
FP-238 2167 ≤50 39

Fan and motor quantities

Model Fans Motors
FP-34 1 1
FP-51 2 1
FP-68 2 1
FP-85 2 1
FP-102 2 1
FP-136 3 2
FP-170 4 2
FP-204 4 2
FP-238 4 2

Input power at high speed

Model 12 Pa (W) 30 Pa (W) 50 Pa (W)
FP-34 22 26 29
FP-51 30 34 40
FP-68 36 42 49
FP-85 44 51 61
FP-102 56 65 80
FP-136 78 91 101
FP-170 88 101 125
FP-204 114 140 173
FP-238 139 166 208

Noise at high speed

Model 12 Pa dB(A) 30 Pa dB(A) 50 Pa dB(A)
FP-34 37 40 42
FP-51 39 42 44
FP-68 41 44 46
FP-85 43 46 47
FP-102 45 47 49
FP-136 46 48 50
FP-170 48 50 52
FP-204 50 52 54
FP-238 52 54 56

Cabinet options

Model Without return-air box (kg) With return-air box (kg)
FP-34 11 14.2
FP-51 12.5 16.3
FP-68 13.5 17.5
FP-85 15 19.5
FP-102 16.5 21.5
FP-136 21.5 27.2
FP-170 28 35
FP-204 35 43
FP-238 39 47.6

Construction and connections

Item Specification
Water circuit 4-pipe system
Coil 3-row coil
Fan type Forward-curved, multi-blade centrifugal fan with double inlet
Motor type Brushless DC motor, 220 V / 50 Hz, built-in AC-DC conversion
Heat exchanger Copper tubes with louvered aluminium fins, mechanically expanded
Water inlet and outlet connections 3/4 inch internal thread
Condensate connection 3/4 inch external thread
Power supply 220 V / 50 Hz

Rated conditions and notes

  1. Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
  2. Heating rating: inlet water temperature 60°C; water flow the same as for cooling; entering air dry-bulb 21.0°C.
  3. Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
  4. For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
  5. Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
  6. For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
  7. The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.

Technical data: Haichuang catalogue, printed pages 41-44.