Ceiling Air Handling Unit

A compact, low-profile duct-mounted air handling unit ideal for modern commercial offices, hotels, and healthcare buildings with limited ceiling space. Constructed with low-vibration centrifugal fans and heavy-duty cooling coils, it provides exceptional indoor air quality, whisper-quiet operation, and easy maintenance access.

Nitelikler Değer
Product type

Air Handling Units

Share your required model and operating conditions for technical review.

Ceiling Air Handling Unit

A compact, low-profile duct-mounted air handling unit ideal for modern commercial offices, hotels, and healthcare buildings with limited ceiling space. Constructed with low-vibration centrifugal fans and heavy-duty cooling coils, it provides exceptional indoor air quality, whisper-quiet operation, and easy maintenance access.

Airflow, fan quantity and noise

Model Airflow (m³/h) Fan sets Noise dB(A)
HCGD010B 1000 1 58
HCGD020B 2000 1 59
HCGD025B 2500 1 59
HCGD030B 3000 1 60
HCGD040B 4000 2 61
HCGD050B 5000 2 62
HCGD060B 6000 2 63
HCGD080B 8000 2 64
HCGD100B 10000 2 68
HCGD125B 12500 2 69
HCGD150B 15000 2 73

External static pressure and fan power

Model 4-row ESP (Pa) 6-row ESP (Pa) 8-row ESP (Pa) Fan power (kW)
HCGD010B 200 150 100 0.32
HCGD020B 200 150 100 0.37
HCGD025B 250 200 150 0.45
HCGD030B 250 200 150 0.55
HCGD040B 250 200 150 0.45 × 2
HCGD050B 300 250 200 0.55 × 2
HCGD060B 300 250 200 0.55 × 2
HCGD080B 300 250 200 1.1 × 2
HCGD100B 350 300 250 1.3 × 2
HCGD125B 350 300 250 1.8 × 2
HCGD150B 400 350 300 2.2 × 2

Unit weight

Model 4-row coil (kg) 6-row coil (kg) 8-row coil (kg)
HCGD010B 66 69 72
HCGD020B 77 81 85
HCGD025B 80 84 89
HCGD030B 92 98 103
HCGD040B 116 124 131
HCGD050B 129 138 147
HCGD060B 142 153 164
HCGD080B 169 183 196
HCGD100B 225 241 257
HCGD125B 249 267 286
HCGD150B 295 317 338

Return-air cooling, 6-row coil

Model Capacity (kW) Water flow (m³/h) Water resistance (kPa)
HCGD010B 8.5 1.62 10.1
HCGD020B 15.2 2.88 11.9
HCGD025B 18.9 3.58 12.5
HCGD030B 22.8 4.32 12.8
HCGD040B 30.2 5.72 13.5
HCGD050B 37.7 7.14 13.6
HCGD060B 45.3 8.57 16.6
HCGD080B 66.4 12.57 16.7
HCGD100B 78.7 14.89 17.8
HCGD125B 91.7 17.36 17.5
HCGD150B 110 20.81 18.5

Return-air heating, 6-row coil

Model Capacity (kW) Water flow (m³/h) Water resistance (kPa)
HCGD010B 15.3 2.89 8.3
HCGD020B 25.3 4.79 11.9
HCGD025B 31.5 5.96 12.5
HCGD030B 38.5 7.29 12.8
HCGD040B 51.8 9.8 13.5
HCGD050B 62.4 11.81 13.6
HCGD060B 75.4 14.27 16.6
HCGD080B 96.1 18.18 16.7
HCGD100B 110.6 20.93 17.8
HCGD125B 151.5 28.67 17.5
HCGD150B 181.7 34.38 18.5

Fresh-air cooling, 6-row coil

Model Capacity (kW) Water flow (m³/h) Water resistance (kPa)
HCGD010B 18.3 3.35 15.5
HCGD020B 31.2 5.72 21.42
HCGD025B 38.8 7.11 22.5
HCGD030B 46.1 8.45 23.04
HCGD040B 63.7 11.67 24.3
HCGD050B 77.3 14.16 24.48
HCGD060B 93.6 17.15 29.88
HCGD080B 121.3 22.22 30.06
HCGD100B 153.3 28.08 32.04
HCGD125B 193.7 35.49 31.56
HCGD150B 240.3 44.02 33.3

Fresh-air heating, 6-row coil

Model Capacity (kW) Water flow (m³/h) Water resistance (kPa)
HCGD010B 17.5 3.31 14.91
HCGD020B 29.5 5.59 21.42
HCGD025B 36.9 6.99 22.5
HCGD030B 45.1 8.54 23.04
HCGD040B 60.3 11.41 24.3
HCGD050B 70.2 13.28 24.48
HCGD060B 88.2 16.69 29.88
HCGD080B 116 21.95 30.06
HCGD100B 142.3 26.92 32.04
HCGD125B 177.7 33.62 30.96
HCGD150B 212.6 40.22 33.3

Fan construction

Item Specification
Fan Outer-rotor direct-drive centrifugal fan

Rating conditions

  1. Return-air cooling: entering air DB 27°C / WB 19.5°C. Fresh-air cooling: DB 35°C / WB 27.5°C. Chilled water inlet 7°C, water temperature difference 5°C.
  2. Return-air heating: entering air DB 15°C. Fresh-air heating: entering air DB 7°C. Heating water inlet 60°C.
  3. Coil performance tables above show the six-row configuration. Four-row and eight-row coils have separate ratings; select the required coil for the project.

Technical data: Haichuang catalogue, printed pages 22-24. B and S identify cabinet and jet-flow versions respectively.

Let’s Build Your HVAC Solution

Contact us for product information, project support or partnership enquiries.