Large Modular Air Handling Unit

Engineered for large-scale commercial and industrial facilities, this modular air handling unit features high-strength thermal break aluminum frames and double-skin insulated panels. It offers flexible functional section combinations, including filtration, cooling, heating, humidification, and heat recovery, delivering high airflow and superior energy efficiency for complex HVAC projects

Atribut Nilai
Product type

Air Handling Units

Share your required model and operating conditions for technical review.

Large Modular Air Handling Unit

Engineered for large-scale commercial and industrial facilities, this modular air handling unit features high-strength thermal break aluminum frames and double-skin insulated panels. It offers flexible functional section combinations, including filtration, cooling, heating, humidification, and heat recovery, delivering high airflow and superior energy efficiency for complex HVAC projects

Selection data below is for the six-row coil, return-air configuration. Four-row, eight-row, fresh-air, steam-heating and pre-heater configurations are selected separately to suit the project.

6-row return-air cooling ratings

Model Airflow (m³/h) Total cooling (kW) Sensible cooling (kW)
HCZKW030T 3050 23 15.4
HCZKW040T 4016 30.8 20.6
HCZKW050T 5020 38.5 25.8
HCZKW060T 6168 46.2 30.9
HCZKW080T 8025 61.5 41.2
HCZKW100T 10068 77.0 51.6
HCZKW120T 12134 92.3 61.8
HCZKW150T 15075 115.4 77.3
HCZKW200T 20082 153.5 102.8
HCZKW250T 25025 191.9 128.5
HCZKW300T 30060 200.3 134.2
HCZKW350T 35350 235.5 157.8
HCZKW400T 40156 267.5 179.2
HCZKW500T 50562 336.9 225.7
HCZKW600T 60280 401.6 269.1
HCZKW800T 84850 534.0 357.8
HCZKW1000T 100260 668.0 447.5
HCZKW1200T 121056 806.5 540.4
HCZKW1400T 140862 938.5 628.8
HCZKW1600T 161236 1074.2 719.7
HCZKW1800T 180650 1203.5 806.4
HCZKW2000T 201260 1340.9 898.4
HCZKW2200T 222152 1480.0 991.6
HCZKW2500T 251882 1678.1 1124.3

6-row cooling coil water and air resistance

Model Air resistance (Pa) Water resistance (kPa) Water flow (m³/h)
HCZKW030T 179 7.3 4
HCZKW040T 178 11.4 5.3
HCZKW050T 192 13.9 6.6
HCZKW060T 196 12.1 7.9
HCZKW080T 188 14.2 10.6
HCZKW100T 198 15.7 13.2
HCZKW120T 201 16.2 15.9
HCZKW150T 196 20.2 19.8
HCZKW200T 200 18.8 26.4
HCZKW250T 208 21.4 33.0
HCZKW300T 196 22.0 34.4
HCZKW350T 201 20.0 40.5
HCZKW400T 192 22.8 46.0
HCZKW500T 198 24.6 57.9
HCZKW600T 195 26.4 69.1
HCZKW800T 211 28.6 91.8
HCZKW1000T 201 33.7 114.9
HCZKW1200T 193 37.4 138.7
HCZKW1400T 198 42.2 161.4
HCZKW1600T 192 49.4 184.7
HCZKW1800T 201 57.4 207.0
HCZKW2000T 201 69.1 230.6
HCZKW2200T 193 76.0 254.5
HCZKW2500T 200 86.4 288.6

6-row return-air heating ratings

Model Heating (kW) Air resistance (Pa) Water resistance (kPa) Water flow (m³/h)
HCZKW030T 34.8 159 6.7 3
HCZKW040T 46.5 158 10.4 4
HCZKW050T 58.1 172 12.8 5
HCZKW060T 69.7 176 11.1 6
HCZKW080T 92.9 168 13.1 8
HCZKW100T 116.2 178 14.4 10
HCZKW120T 139.3 181 14.9 12
HCZKW150T 174.2 176 18.5 15
HCZKW200T 231.8 180 17.3 19.9
HCZKW250T 289.7 188 19.3 24.9
HCZKW300T 302.4 176 20.2 26
HCZKW350T 355.6 181 18.3 30.6
HCZKW400T 404.0 172 20.9 34.7
HCZKW500T 508.7 178 22.6 43.7
HCZKW600T 606.4 175 24.2 52.1
HCZKW800T 806.4 191 26.3 69.3
HCZKW1000T 1008.6 181 31.0 86.7
HCZKW1200T 1217.8 173 34.3 104.6
HCZKW1400T 1417.1 178 38.8 121.8
HCZKW1600T 1622.0 172 45.3 139.4
HCZKW1800T 1817.4 181 52.7 156.1
HCZKW2000T 2024.7 181 63.5 174.0
HCZKW2200T 2234.9 173 69.8 192.0
HCZKW2500T 2534.0 180 79.3 217.7

Construction and functional sections

Item Specification
Frame Aluminium alloy frame
Panels Double-skin insulated panels
Functional sections Air mixing, filtration, cooling, heating, humidification and heat recovery, as selected for the project
Configuration Modular combinations to suit the required air treatment process

Rating conditions

  1. Cooling: entering air dry-bulb 27°C and wet-bulb 19.5°C, chilled water inlet/outlet 7°C / 12°C.
  2. Heating: entering air dry-bulb 15°C, inlet water 60°C, inlet/outlet water temperature difference 10°C.
  3. The tables show catalogue selection data for the stated coil and air conditions. Functional sections, fan selection and final dimensions depend on the project.

Technical data: Haichuang catalogue, printed pages 15-20. Six-row return-air values shown from pages 15 and 17.