Standard Cassette Fan Coil Unit
Designed for ceiling installation with a 360-degree airflow panel, ensuring uniform temperature distribution, quiet operation, and a sleek appearance that seamlessly blends into commercial and office spaces.
Cassette type with condensate lift pump
H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.
Rated airflow
| Model |
High (m³/h) |
Medium (m³/h) |
Low (m³/h) |
| FP-34 |
340 |
260 |
170 |
| FP-51 |
510 |
390 |
260 |
| FP-68 |
680 |
510 |
340 |
| FP-85 |
850 |
640 |
430 |
| FP-102 |
1020 |
770 |
510 |
| FP-136 |
1360 |
1020 |
680 |
| FP-170 |
1700 |
1280 |
850 |
| FP-204 |
2040 |
1530 |
1020 |
| FP-238 |
2380 |
1790 |
1190 |
High-speed performance
| Model |
Cooling (W) |
Heating (W) |
Input (W) |
Noise dB(A) |
| FP-34 |
2000 |
2800 |
46 |
37 |
| FP-51 |
2700 |
4200 |
50 |
39 |
| FP-68 |
3700 |
5600 |
55 |
41 |
| FP-85 |
4500 |
7000 |
66 |
43 |
| FP-102 |
5600 |
8400 |
75 |
45 |
| FP-136 |
7000 |
11200 |
123 |
46 |
| FP-170 |
9100 |
13900 |
138 |
48 |
| FP-204 |
10800 |
16700 |
189 |
50 |
| FP-238 |
12600 |
19500 |
215 |
52 |
Capacity in kcal/h
| Model |
Cooling |
Heating |
| FP-34 |
1720 |
2408 |
| FP-51 |
2322 |
3612 |
| FP-68 |
3182 |
4816 |
| FP-85 |
3870 |
6020 |
| FP-102 |
4816 |
7224 |
| FP-136 |
6020 |
9632 |
| FP-170 |
7826 |
11954 |
| FP-204 |
9288 |
14362 |
| FP-238 |
10836 |
16770 |
Water circuit and weight
| Model |
Water flow (kg/h) |
Pressure loss (kPa) |
Weight (kg) |
| FP-34 |
344 |
≤30 |
20 |
| FP-51 |
464 |
≤30 |
20 |
| FP-68 |
636 |
≤30 |
20 |
| FP-85 |
774 |
≤30 |
27.5 |
| FP-102 |
963 |
≤40 |
28 |
| FP-136 |
1204 |
≤40 |
28 |
| FP-170 |
1565 |
≤40 |
35.5 |
| FP-204 |
1857 |
≤40 |
36.5 |
| FP-238 |
2167 |
≤50 |
36.5 |
Fan and motor quantities
| Model |
Fans |
Motors |
| FP-34 |
1 |
1 |
| FP-51 |
1 |
1 |
| FP-68 |
1 |
1 |
| FP-85 |
1 |
1 |
| FP-102 |
1 |
1 |
| FP-136 |
1 |
1 |
| FP-170 |
1 |
1 |
| FP-204 |
1 |
1 |
| FP-238 |
1 |
1 |
Construction and connections
| Item |
Specification |
| Water circuit |
2-pipe system |
| Fan type |
Centrifugal fan wheel |
| Motor |
Capacitor-run asynchronous motor, IP20 / Class B |
| Heat exchanger |
Copper tubes with louvered aluminium fins, mechanically expanded |
| Condensate lift |
1200 mm |
| Control |
Remote control / wired control |
| Water connections |
3/4 inch external thread |
| Condensate connection |
Φ20 |
| Power supply |
220 V / 50 Hz |
Rated conditions and notes
- Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
- Heating rating: inlet water temperature 60°C; water flow the same as for cooling; entering air dry-bulb 21.0°C.
- Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
- For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
- Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
- For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
- The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.
Alternative catalogue configuration: self-draining cassette
H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.
Rated airflow
| Model |
High (m³/h) |
Medium (m³/h) |
Low (m³/h) |
| FP-34 |
340 |
260 |
170 |
| FP-51 |
510 |
390 |
260 |
| FP-68 |
680 |
510 |
340 |
| FP-85 |
850 |
640 |
430 |
| FP-102 |
1020 |
770 |
510 |
| FP-136 |
1360 |
1020 |
680 |
| FP-170 |
1700 |
1280 |
850 |
| FP-204 |
2040 |
1530 |
1020 |
| FP-238 |
2380 |
1790 |
1190 |
High-speed performance
| Model |
Cooling (W) |
Heating (W) |
Input (W) |
Noise dB(A) |
| FP-34 |
2000 |
2800 |
34 |
37 |
| FP-51 |
2700 |
4200 |
38 |
38 |
| FP-68 |
3700 |
5600 |
43 |
41 |
| FP-85 |
4500 |
7000 |
54 |
43 |
| FP-102 |
5600 |
8400 |
63 |
45 |
| FP-136 |
7000 |
11200 |
111 |
46 |
| FP-170 |
9100 |
13900 |
126 |
48 |
| FP-204 |
10800 |
16700 |
177 |
50 |
| FP-238 |
12600 |
19500 |
203 |
52 |
Capacity in kcal/h
| Model |
Cooling |
Heating |
| FP-34 |
1720 |
2408 |
| FP-51 |
2322 |
3612 |
| FP-68 |
3182 |
4816 |
| FP-85 |
3870 |
6020 |
| FP-102 |
4816 |
7224 |
| FP-136 |
6020 |
9632 |
| FP-170 |
7826 |
11954 |
| FP-204 |
9288 |
14362 |
| FP-238 |
10836 |
16770 |
Water circuit and weight
| Model |
Water flow (kg/h) |
Pressure loss (kPa) |
Weight (kg) |
| FP-34 |
344 |
≤30 |
25 |
| FP-51 |
464 |
≤30 |
25 |
| FP-68 |
636 |
≤30 |
25 |
| FP-85 |
774 |
≤30 |
32 |
| FP-102 |
963 |
≤40 |
32 |
| FP-136 |
1204 |
≤40 |
32 |
| FP-170 |
1565 |
≤40 |
43 |
| FP-204 |
1857 |
≤40 |
43 |
| FP-238 |
2167 |
≤50 |
43 |
Fan and motor quantities
| Model |
Fans |
Motors |
| FP-34 |
1 |
1 |
| FP-51 |
1 |
1 |
| FP-68 |
1 |
1 |
| FP-85 |
1 |
1 |
| FP-102 |
1 |
1 |
| FP-136 |
1 |
1 |
| FP-170 |
1 |
1 |
| FP-204 |
1 |
1 |
| FP-238 |
1 |
1 |
Construction and connections
| Item |
Specification |
| Water circuit |
2-pipe system |
| Fan type |
Centrifugal fan wheel |
| Motor |
Capacitor-run asynchronous motor, IP20 / Class B |
| Heat exchanger |
Copper tubes with louvered aluminium fins, mechanically expanded |
| Water connections |
3/4 inch external thread |
| Condensate connection |
Φ30 |
| Power supply |
220 V / 50 Hz |
Rated conditions and notes
- Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
- Heating rating: inlet water temperature 60°C; water flow the same as for cooling; entering air dry-bulb 21.0°C.
- Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
- For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
- Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
- For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
- The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.
Technical data: Haichuang catalogue, printed pages 49-51. Pump and self-draining versions are separate configurations; confirm the required version before ordering.