Cassette type with condensate lift pump

H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.

Rated airflow

Model High (m³/h) Medium (m³/h) Low (m³/h)
FP-34 340 260 170
FP-51 510 390 260
FP-68 680 510 340
FP-85 850 640 430
FP-102 1020 770 510
FP-136 1360 1020 680
FP-170 1700 1280 850
FP-204 2040 1530 1020
FP-238 2380 1790 1190

High-speed performance

Model Cooling (W) Heating (W) Input (W) Noise dB(A)
FP-34 2000 2800 46 37
FP-51 2700 4200 50 39
FP-68 3700 5600 55 41
FP-85 4500 7000 66 43
FP-102 5600 8400 75 45
FP-136 7000 11200 123 46
FP-170 9100 13900 138 48
FP-204 10800 16700 189 50
FP-238 12600 19500 215 52

Capacity in kcal/h

Model Cooling Heating
FP-34 1720 2408
FP-51 2322 3612
FP-68 3182 4816
FP-85 3870 6020
FP-102 4816 7224
FP-136 6020 9632
FP-170 7826 11954
FP-204 9288 14362
FP-238 10836 16770

Water circuit and weight

Model Water flow (kg/h) Pressure loss (kPa) Weight (kg)
FP-34 344 ≤30 20
FP-51 464 ≤30 20
FP-68 636 ≤30 20
FP-85 774 ≤30 27.5
FP-102 963 ≤40 28
FP-136 1204 ≤40 28
FP-170 1565 ≤40 35.5
FP-204 1857 ≤40 36.5
FP-238 2167 ≤50 36.5

Fan and motor quantities

Model Fans Motors
FP-34 1 1
FP-51 1 1
FP-68 1 1
FP-85 1 1
FP-102 1 1
FP-136 1 1
FP-170 1 1
FP-204 1 1
FP-238 1 1

Construction and connections

Item Specification
Water circuit 2-pipe system
Fan type Centrifugal fan wheel
Motor Capacitor-run asynchronous motor, IP20 / Class B
Heat exchanger Copper tubes with louvered aluminium fins, mechanically expanded
Condensate lift 1200 mm
Control Remote control / wired control
Water connections 3/4 inch external thread
Condensate connection Φ20
Power supply 220 V / 50 Hz

Rated conditions and notes

  1. Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
  2. Heating rating: inlet water temperature 60°C; water flow the same as for cooling; entering air dry-bulb 21.0°C.
  3. Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
  4. For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
  5. Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
  6. For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
  7. The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.

Alternative catalogue configuration: self-draining cassette

H = high speed, M = medium speed, L = low speed. Cooling and heating capacities are rated at high speed under the conditions below.

Rated airflow

Model High (m³/h) Medium (m³/h) Low (m³/h)
FP-34 340 260 170
FP-51 510 390 260
FP-68 680 510 340
FP-85 850 640 430
FP-102 1020 770 510
FP-136 1360 1020 680
FP-170 1700 1280 850
FP-204 2040 1530 1020
FP-238 2380 1790 1190

High-speed performance

Model Cooling (W) Heating (W) Input (W) Noise dB(A)
FP-34 2000 2800 34 37
FP-51 2700 4200 38 38
FP-68 3700 5600 43 41
FP-85 4500 7000 54 43
FP-102 5600 8400 63 45
FP-136 7000 11200 111 46
FP-170 9100 13900 126 48
FP-204 10800 16700 177 50
FP-238 12600 19500 203 52

Capacity in kcal/h

Model Cooling Heating
FP-34 1720 2408
FP-51 2322 3612
FP-68 3182 4816
FP-85 3870 6020
FP-102 4816 7224
FP-136 6020 9632
FP-170 7826 11954
FP-204 9288 14362
FP-238 10836 16770

Water circuit and weight

Model Water flow (kg/h) Pressure loss (kPa) Weight (kg)
FP-34 344 ≤30 25
FP-51 464 ≤30 25
FP-68 636 ≤30 25
FP-85 774 ≤30 32
FP-102 963 ≤40 32
FP-136 1204 ≤40 32
FP-170 1565 ≤40 43
FP-204 1857 ≤40 43
FP-238 2167 ≤50 43

Fan and motor quantities

Model Fans Motors
FP-34 1 1
FP-51 1 1
FP-68 1 1
FP-85 1 1
FP-102 1 1
FP-136 1 1
FP-170 1 1
FP-204 1 1
FP-238 1 1

Construction and connections

Item Specification
Water circuit 2-pipe system
Fan type Centrifugal fan wheel
Motor Capacitor-run asynchronous motor, IP20 / Class B
Heat exchanger Copper tubes with louvered aluminium fins, mechanically expanded
Water connections 3/4 inch external thread
Condensate connection Φ30
Power supply 220 V / 50 Hz

Rated conditions and notes

  1. Cooling rating: inlet/outlet water temperatures 7°C / 12°C; entering air dry-bulb 27.0°C and wet-bulb 19.5°C.
  2. Heating rating: inlet water temperature 60°C; water flow the same as for cooling; entering air dry-bulb 21.0°C.
  3. Noise values were measured in a fully anechoic chamber with background noise of 16.5 dB(A), according to GB/T 19232-2019, as stated in the catalogue.
  4. For low-static-pressure units, the catalogue specifies 0 Pa outlet static pressure with air outlet and filter, and 12 Pa without air outlet and filter.
  5. Input power is the power consumed under the reference operating condition. Motor nameplate power is the nominal motor output power.
  6. For operating conditions different from the rated conditions, use the correction factors in the manufacturer’s catalogue. Actual cooling or heating capacity = rated capacity × operating-condition correction factor.
  7. The manufacturer reserves the right to modify the design for product improvement without prior notice. Refer to the actual supplied product.

Technical data: Haichuang catalogue, printed pages 49-51. Pump and self-draining versions are separate configurations; confirm the required version before ordering.